Lutron RMJS-20R-DV-B Vive PowPak Wireless Receptacle Control Relay Module
RMJS-20R-DV-B
Please call us at 877-487-4444 to purchase this product or email us at buyriteelectric@gmail.com
The PowPak 20 A Relay Receptacle Control Module is aradio-frequency (RF), receptacle switching solution that is capable of controlling 20 A receptacles based on input from Pico remote controls and Radio Powr Savr occupancy sensors.
Communication with RF input devices, such as Pico remote controls and/or Radio Powr Savr occupancy / vacancy sensors, is accomplished using Lutron Clear Connect RF Technology.
These products are also compatible with the Vive hub which enables a simple setup process using a standard web browser on any Wi-Fi enabled phone, tablet or computer. The hub also enables control and monitoring of all Vive devices. The Vive hub can be added at any time. System reprogramming will be required. For a complete list of features supported with the Vive hub, see specification submittal 369902.
FEATURES:
Softswitch: Lutron patented technology prevents arcing of relay contacts, extending product lifetime
Optional low-voltage dry contact closure output provides integration to HVAC, VAV, etc.
Receives wireless inputs from up to 10 Pico remote controls, and 10 Radio Powr Savr occupancy / vacancy sensors
RoHS Compliant
Able to control 20 A receptacles
Capable of switching general-purpose loads
Utilizes Lutron Clear Connect RF Technology
Mounts to a U.S. style junction box through a standard 1/2 in (12.7 mm) size knockout
Includes required controlled outlet labels for code compliance
SPECIFICATIONS:
UL® 508 Listed (USA)
FCC approved. Complies with the limits for a Class B device, pursuant to Part 15 of the FCC rules. (USA)
IC (Canada)
CSA compliant (Canada)
NOM and COFETEL compliant (Mexico)
Complies with requirements for use in other spaces used for environmental air (plenums) per NEC® 2014 300.22(C)(3)
Listed in accordance to CAN/ULC S102.2-2010 with a Flame Spread Rating of 0 and a Smoke Developed Classification of 40, with a minimum spacing of 6 ft (1.83 m) off center
120 /277 V~ 50 / 60 Hz
Standby Power Consumption (all models): < 1.25 W
Ambient operating temperature: 32 °F to 131 °F (0 °C to 55 °C)
0% to 90% humidity, non-condensing
For indoor use only
All drivers and ballasts used with Vive wireless controls must comply with the limits for a Class A device pursuant to Part 15 of the FCC Rules